Parallel
operation describes a configuration whereby the outputs of two or more
uninterruptible power supply modules are connected to supply the load via a common
ac bus bar(copper
bus bar ampacity). For it to be
successful each UPS module must be capable of parallel operation and not all
are. To work in this configuration, modules need to be fitted with parallel
cards, which are then interlinked via opto-isolator cables to form a closed
loop data communication system. This allows data to be exchanged between the
control sections of each uninterruptible power supply module. They can still be
operated in isolation if necessary but the card will enable the whole group to
be operated as one system. A group of parallel UPS modules like this is
referred to as a UPS system and there are two basic configurations:
parallel-redundancy and parallel-capacity.
Parallel-redundant
System (N+X):
Parallel-redundant
UPS is the most commonly utilized parallel configuration and is usually used to
protect mission-critical applications within data centers, industrial sites and
large service operators that require the highest levels of resilience and
availability.
The number of
uninterruptible power supply modules that can be operated in parallel varies
between UPS manufacturer but a common standard is up to eight. In some cases,
maximum MTBF and resilience system can be improved by a factor of ten in
comparison to a single UPS configuration.
Parallel-capacity
System (N):
A
parallel-capacity uninterruptible power supply system is comprised of multiple
UPS working in parallel but without redundancy. Capacity systems do not
therefore increase system resilience but they can be less costly to install.
However, the primary advantage of a parallel-redundant system over a
parallel-capacity system, particularly for mission-critical applications, is
during maintenance and/or repair. A parallel-redundant solution allows
maintenance work to be carried out without disruption to the load whereas in a
parallel-capacity configuration the entire UPS system must be bypassed to allow
individual modules to be worked on. The total capacity of the UPS system in a
parallel-capacity system is derived from the total number of UPS modules used
in a configuration also known as a Total Power System.
Sizing UPS in
parallel configuration is critical:
The key to
designing a parallel UPS system is sizing. The whole system needs to be sized
so as to negate overloads should any one module fail. This will entail a degree
of over-sizing, which is always preferable to running close to design limits
with potential overloads.
During normal
operation, when incoming mains power supply (or generated supply) is present,
each of the uninterruptible power supply modules in both a parallel-redundant
and a parallel-capacity system will share the load equally. This is also true
when operating in battery mode. Each module has its own battery set rather than
a shared common battery and each, therefore, should have the same runtime
duration and dc cut off voltage threshold.
Should any of
the UPS modules detect an internal fault they will automatically disconnect
from the common output ac bus bar(aluminum bus bar
suppliers) and the
remaining UPS modules will share the load equally without disruption in supply.
If a second
uninterruptible power supply module in the system should fail concurrently, the
remaining operational module/s will be forced into overload and the load
transferred to a bypass supply via the static-switch. This will simultaneously
force the two faulty modules into bypass but will ensure the load receives an
adequate source of power automatically and without disruption.
When in bypass,
system resilience is reduced and the load will be connected to raw mains supply
or an alternative source of ac power. On bypass, each UPS will generate alarm
notification, which can be captured at local network or remote site levels.
Dual Input
Supplies:
Resilience of
parallel UPS configurations can be further enhanced using dual input supplies.
Here the UPS system is supplied from separate rectifier and static-switch
supplies.
Uninterruptible
power supply installations generally rely on common mains power supplies
feeding both the UPS and static bypass. It creates a single-point-of-failure,
however, which is unacceptable in mission-critical applications. Using dual
input supplies, from separately derived sources (even separate substations),
removes this problem.
For
installations in which power protection is critical, parallel UPS configuration
is an ideal option but systems must be designed from the outset with capacity,
resilience, redundancy and maintenance firmly in mind.